NAMCO's Sizing Guide will help you choose the correct pressure for your booster system. The first step is to determine if a booster system is needed. Using the chart in Figure 1, calculate the total head required. This will determine if a pumping station is needed on the site.
Calculate Pressure Required
Total Height of building from pumps
__________ (+) #1__________ft.
(From pump to highest point for water)
Pipe pressure loss (8 ft. min. or 10% of static head) (+) #2__________ft.
Pressure Required @ top of building (81 ft. normal) (+) #3__________ft.
Total Head Required @ system discharge (Total 1-3) (+) #4__________ft.
Pumping system pressure loss (+) #5__________ft.
Total Head for system (Total #4 & #5) Subtotal #6__________ft.
Less Minimum Suction pressure (-) #7__________ft.
Suction lift (+) #8__________ft.
Total pump head required
ft. head = Head in
psig
__________PSIG = #9__________ft.
2.31